1250A

Technical Specifications

Specifications of ATS cabinets

Type Switch circuit and Motor

Assembler Tanky

Origin Vietnam

Voltage 380/220V

Rated current 1250A

Frequency 50Hz

Specifications of the power adapter

Rated insulation voltage Ui (V) 1000

Rated impulse withstand voltage Uimp (kV) 12

Rated short-time withstand current 1s Icw (kA rms) 35

Rated short-circuit making capacity (kA peak) 73.5

Prospective short-circuit current (kA rms) 100

Associated fuse rating (A) 1250

Minimum Cu cable cross-section (mm2) -

Minimum Cu busbar cross-section (mm2) 2x60x5

Maximum Cu cable cross-section (mm2) 4x185

Maximum Cu busbar width (mm) 63

Tightening torque mini/maxi (Nm) 20/26

Switching time I-II or II-I (s) 2.6

Switching time I-0 or II-0 (s) 1.6

Duration of "electrical blackout" I-II (s) minimum 1.5

Power supply min/max (VAC) 166/332

Power supply 230 VAC inrush / nominal (VA) - ATyS 460/184

Durability (number of operating cycles) 4000

Standard IEC 60947-6-1

Weight ATyS 4 P (kg) 33.6

Weight ATyS d 4 P (kg) 34.2